TOXFREE ZH YMz1Kf
Description
An LSHF safety cable is TOXFREE ZH YMz1Kf. Toxic and corrosive gasses are not released in the case of a fire, protecting both people and electronic equipment from harm. Due to this, it is strongly advised for usage in public spaces including healthcare facilities, educational institutions, museums, transportation hubs, retail centers, offices, and labs.
Results of the TOXFREE ZH YMz1Kf connecting wire
Electrical efficiency
Reduced Power 1,6/1 kilovolt
Standard
standards (IEC 60502-1 / UNE 21123-4)
Green Lights
CE, RoHS, AENOR, SEC, KEMA KEUR, and more
Regulation of Construction Products (CPR)
According to the cross-section, B2ca s1a, d1, and a1 or Cca s1a, d1, and a1
Heating efficiency
Conductor temperature maximum: 90ºC.
Maximum temperature for a short circuit: 250ºC (maximum 5 seconds).
When it comes to fixed and protected installations, the minimum service temperature is -40ºC.
A temperature of -0ºC is required for installation and handling.
Functionality of fire
Prevention of flame propagation in accordance with EN 60332-1/IEC 60332-1.
Compliance with fire prevention standards as outlined in EN 60332-3/IEC 60332-3 and EN 50399.
Conforms to LSHF standards as outlined in EN 60754-1/IEC 60754-1.
Light transmittance > 80%; low smoke emission according to UNE-EN 61034 and IEC 61034.
Conforms to EN 60754-2/IEC 60754-2 standards for low corrosive gas emissions.
According to EN 50575, the reaction to fire CPR can be B2ca s1a, d1, a1 or Cca s1a, d1, a1 (see to the cross-section).
Functional capability
Radius of minimum bending: x5 of the diameter of the cable.
Rage against impacts: AG2 Moderate.
Efficiency in environmental maintenance
Acceptable chemical and oil resistance.
UV Resistant to the standards set by EN 50618.
The AD8 Submersion is water-resistant.
Other
Marking each meter individually.
Setting requirements for installation
Enjoy the outdoors.
Buried.
Through the medium.
Use case
Commercial application.
Open areas.
Product presentation
You can find it in barrels or on rolls that are 100 meters long.
The design of the TOXFREE ZH YMz1Kf cable
Musical director
Class 5 (flexible) electrolytic annealed copper conductor in accordance with EN and IEC 60228.
Keeping heat in
Types of cross-linked polyethylene (XLPE) and (DIX-3) as per IEC 60502-1 and HD 603, respectively. The following is the standard way that insulated conductors are identified according to HD 308:
(1) All-Natural
brown plus two blue
3. Green/Yellow + Brown + 3 G-Blue
× three brown, black, and grey
brown, black, grey, and blue (reduced cross-section) multiplied by three plus one
Four-Grey, Brown, Black, and Green/Yellow
4 times each of brown, black, grey, and blue
5-Grey, 5-Black, 5-Blue, 5-Green/Yellow
6 GB or greaterGreen and yellow with black numbers
Veil exterior
Type DMZ-E in accordance with UNE 21123-4 and Low Smoke Halogen Free (LSHF) polyolefin in accordance with IEC 60502-1 are the specifications for the outer sheath. Color green.
LOW VOLTAGE 0,6/1kV
Maximum conductor temperature: 90ºC.
Water resistance: AD5 Jets
Flame non-propagation based on EN 60332-1 and IEC 60332-1
Industrial use / Public places.
Technology
1. Conductor
Electrolytic annealed copper conductor, class 5 (flexible), based on EN 60228 and IEC 60228.
2. Insulation
Cross-linked polyethylene (XLPE) according to IEC 60502-1.
The standard identification of insulated conductors according to HD 308 is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Yellow/green
3 x Brown + Black + Grey
3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)
4 G Brown + Black + Grey + Yellow/green
4 x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Blue + Yellow/green
3. Outer sheath
Low Smoke Halogen Free (LSHF) polyolefin. Black colour.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
- Chemical & Oil resistance: Acceptable.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
MECHANICAL PERFORMANCE
- Impact resistance: AG2 Medium severity.
- Minimum bending radius: x5 cable diameter.
WATER RESISTANCE
- Water resistance: AD8 Submersion.
CHEMICAL PERFORMANCE
- UV Resistant based on EN 50618.
FIRE PERFORMANCE
- Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.
- Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
- Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.
- Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.
THERMAL PERFORMANCE
- Impact resistance: AG2 Medium severity.
- Minimum bending radius: x5 cable diameter.
APPROVALS
- CE
- KEMA KEUR
INSTALLATION CONDITIONS
- Buried
- In conduit.
- Open Air.
National norm / European:
- UNE-EN 60332-1
CONSTRUCTION PRODUCT REGULATION
- B2ca s1a, d1, a1
BASED ON
- IEC 60502-1
International norm
- IEC 60502-1
OTHERS
- Meter by meter marking.