TOXFREE ZH RZ1FZ1-K (AS)
Description
An armored LSZH safety cable is TOXFREE ZH RZ1FZ1-K AS. It does not release harmful or corrosive gases in the event of a fire, safeguarding the public's health and preventing potential harm to electronic devices. Its use is therefore strongly advised for public areas, rodent-infested installations, and installations in general where there is a chance of mechanical aggression to the cable.
Performance of the TOXFREE ZH RZ1FZ1-K AS cable
Electrical functionality
MINIMUM VOLTAGE 0,6/1kV
Typical
UNE 21123-4 and IEC 60502-1
Acceptances
CE
RoHS
Regulation of CPR Construction Products
Cca-s1b, d1, a1
Thermal efficiency
90ºC is the maximum conductor temperature.
250ºC is the maximum short-circuit temperature (maximum 5 s).
-40ºC is the minimum service temperature for protected and fixed installations.
Performance of fire
non-propagation of flames according to IEC 60332-1 and EN 60332-1.
non-propagation of fire according to IEC 60332-3 and EN 60332-3.
Low Smoke Zero Halogen, or LSZH, is based on IEC 60754-1 and EN 60754-1.
According to EN 61034 and IEC 61034, low smoke emissions: Transmittance of light > 60%
low emissions of corrosive gases in accordance with IEC 60754-2 and EN 60754-2.
Performance of mechanical systems
A cable diameter of x10 is the minimum bending radius.
AG4 High severity is the impact resistance rating.
Proof against rodents
Performance of chemicals
Resistance to chemicals and oil: Acceptable.
Resistance to UV: EN 50618.
Performance of water
AD5 Jets are water resistant.
Other
marking from meter to meter.
Uses
industrial application.
Design of TOXFREE ZH RZ1FZ1-K AS cable
The conductor
Class 5 (flexible) electrolytically annealed copper, according to EN 60228 and IEC 60228.
Insulation
XLPE, or cross-linked polyethylene.
In accordance with HD 308, insulated conductors are typically identified as follows:
One Natural
Two x Brown + Blue
3 G Green/yellow + Brown + Blue
Three x Black + Grey + Brown
4 G: Green/yellow + Black + Grey + Brown
Four times: Brown, Black, Grey, and Blue
5 G: Green/yellow + Blue + Grey + Black + Brown
At least six black-numbered plus green or yellow
Sheath of separation
Polyolefin inner sheath with low smoke zero halogen (LSZH) properties.
Armor
Double tape armour made of steel or aluminum. Single-core cables use aluminum armor to prevent parasite currents that could cause the cable to overheat. The multicore cables are made of steel tape.
External sheath
IEC 60502-1 classifies Low Smoke Zero Halogen (LSZH) polyolefins as type ST8, while UNE 21123-4 classifies them as type DMZ-E. Green, fire-retardant, and non-toxic.
LOW VOLTAGE 0,6/1kV
Maximum conductor temperature: 90ºC.
Industrial use.
Flame non-propagation based on EN 60332-1 and IEC 60332-1
EN 60332-1 / EN 60332-3 / EN 50267-1 / EN 50267-2 / EN 61034
Technology
1. Class 5 (flexible) conductor electrolytic copper, according to EN and IEC 60228.
2. Cross-linked polyethylene (XLPE) insulation.
Insulated conductors are typically identified as follows:
One Natural
Two x Brown + Blue
3 G Green/Yellow + Brown + Blue
Three x Brown, Black, and Grey
4 G Yellow/green + Black + Grey + Brown
Four times: Brown, Black, Grey, and Blue
Five grams of brown, black, grey, blue, and yellow/green
At least six black-numbered plus green or yellow
3. Low smoke zero halogen (LSZH) polyolefin inner sheath for armor bedding.
4. Armour Double tape armour made of steel or aluminium. Single-core cables use aluminum armor to prevent parasite currents that could cause the cable to overheat. The multicore cables are made of steel tape.
5. Low Smoke Zero Halogen (LSZH) polyolefin type ST8 for the outer sheath, in accordance with IEC 60502-1, and type DMZ-E for UNE 21123-4. Non-toxic, fire retardant, and green in color.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
- Chemical & Oil resistance: Acceptable.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
MECHANICAL PERFORMANCE
- Impact resistance: AG4 High severity.
- Minimum bending radius: x10 cable diameter.
- Rodent proof
WATER RESISTANCE
- Water resistance: AD5 Jets.
CHEMICAL PERFORMANCE
- UV Resistant based on EN 50618.
FIRE PERFORMANCE
- Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.
- Flame non-propagation based on EN 60332-1 and IEC 60332-1
-
Low corrosive gases emission
based on UNE-EN 60754-2 and IEC 60754-2. - Low corrosive gases emission according to IEC 60754-2
- Low smoke halogen free according to IEC 60754-1
- Reaction to fire CPR: Cca-s1b, d2, a1 according to EN 50575.
THERMAL PERFORMANCE
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum service temperature: -40ºC (fixed and protected installations)
APPLICATIONS
- Industrial use.
INSTALLATION CONDITIONS
- Buried
- In conduit.
- Open Air.
CONSTRUCTION PRODUCT REGULATION
- Cca s1a, d1, a1
International norm
- IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034
APPROVALS
- CE
- RoHS
BASED ON
- IEC 60502-1 / UNE 21123-4
National norm / European:
- EN 60332-1 / EN 60332-3 / EN 50267-1 / EN 50267-2 / EN 61034
OTHERS
- Meter by meter marking.