TOXFREE ZH ES05Z1-K & H07Z1-K (AS)
Description
An LSHF safety cable is TOXFREE ZH ES05Z1-K and H07Z1-K (AS). It doesn't release corrosive or hazardous gases in the case of a fire, protecting humans and electronic devices from potential harm. It is therefore strongly advised for usage in public settings like hospitals, schools, museums, bus terminals, airports, shopping centres, offices, labs, etc.
Performance of TOXFREE ZH ES05Z1-K and H07Z1-K (AS) cables
Electrical functionality
MINIMUM VOLTAGE 450/750 V · 300/500 V
RATED VOLTAGE H07Z1-K (from 1,5 mm2 onwards): 450/750 V · ES05Z1-K/H05Z1-K (up to 1 mm2): 300/500 V.
Typical
331 EN 50525 UNE 211002
Acceptances
HAR, CE, RoHS, UKCA, AENOR
Regulation of CPR Construction Products
S1a, d1, and a1 B2ca (cable H07Z1-K)
Thermal efficiency
According to EN 50525-3-31, the maximum conductor temperature is 70ºC.
160ºC is the maximum short-circuit temperature (maximum 5 s).
-40ºC is the minimum service temperature for shielded and permanent installations.
Performance of fire
non-propagation of flames according to IEC 60332-1 and EN 60332-1.
non-propagation of fire according to IEC 60332-3 and EN 60332-3.
In accordance with EN 60754-1 and IEC 60754-1, LSHF stands for Low Smoke Halogen Free.
According to EN 61034 and IEC 61034, low smoke emissions: Transmittance of light > 80%
low emissions of corrosive gases in accordance with IEC 60754-2 and EN 60754-2.
According to EN 50575, the response to fire CPR is B2ca s1a, d1, a1 (cable H07Z1-K).
Performance of mechanical systems
A minimum cable diameter of x5 is required for bending.
Performance of chemicals
Resistance to chemicals and oil: Acceptable.
Other
Marker from meter to meter. (starting at 10 mm2)
Uses
Use in the home.
Wiring for electrical panels.
Public areas.
Packing
In highly resistant boxes, small cross sections (ranging from 0.75 mm2 to 6 mm2) are included. 100 m sealed coils of medium cross sections (ranging from 10 mm2 to 35 mm2) are provided. Drums are used to supply larger cross sections (>35 mm2).
Design of TOXFREE ZH ES05Z1-K and H07Z1-K (A)S cables
Class 5 (flexible) electrolytically annealed copper, according to EN 60228 and IEC 60228.
Conductor
Electrolytic annealed copper, class 5 (flexible), based on EN 60228 and IEC 60228.
Insulation
UNE 211002 classifies polyolefin as type TIZ1, while EN 50363-7 classifies it as type TI7. It is halogen-free and produces little smoke in a fire.
Insulated conductors are typically identified as follows:
The colour blue Brown, RAL 5015 RAL 8003: Black Red (RAL 9005) RAL 3000: Yellow/Green Grey RAL 6018 / 1021 Dark blue, or RAL 7000 White, RAL 5010 RAL 9010.
Additional colours can be requested.
LOW VOLTAGE 300/500 V · 450/750 V
Domestic use / Electrical panel wiring / Public places
EN 50525-3-31 / UNE 211002
Maximum service temperature: 70ºC (EN 50525-3-31).
AENOR / HAR / CE / RoHS / UKCA
UNE-EN 60332-1
B2ca s1a, d1, a1 (cable H07Z1-K)
UNE-EN 60332-1
Technology
1. Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
2. Insulation
Type TIZ1 in accordance with UNE 211002 and type TI7 in accordance with EN 50363-7 are polyolefin materials that are halogen-free and emit minimal fumes in fire conditions.
Insulated conductors are typically identified by the following:
Blue RAL 5015- Brown RAL 8003- Black RAL 9005- Yellow/green RAL 3000 -Red Grey RAL 1021 / RAL 6018- Grey RAL 7000-
Dark blue White RAL 5010- Dark RAL 9010
Additional colours are available upon request.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
-
Chemical
Oil resistance: Acceptable.
FIRE PERFORMANCE
- Fire non-propagation based on EN 60332-3-22 and IEC 60332-3-22.
- Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Low corrosive gases emission according to IEC 60754-2
- Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.
- Low smoke halogen free according to IEC 60754-1
- Reaction to fire CPR: B2ca-s1a, d1, a1 according to EN 50575.
MECHANICAL PERFORMANCE
- Minimum bending radius: x5 cable diameter.
ELECTRICAL PERFORMANCE
- Rated Voltage: H05V-K (up to 1 mm2): 300/500 V. H07V-K (from 1,5 mm2 onwards): 450/750 V.
THERMAL PERFORMANCE
- Maximum service temperature: 70ºC (HD) / 90ºC (UL).
- Maximum short-circuit temperature: 160ºC (max. 5 s).
- Minimum service temperature: -40ºC (fixed and protected installations)
APPROVALS
- AENOR
- CE
- HAR
- RoHS
- UKCA
PACKAGING
- High-resistant crates are used to supply small cross sections, which range from 0.75 mm2 to 6 mm2. Medium cross sections (ranging from 10 mm2 to 35 mm2) are supplied in sealed bundles of 100 m. Drums are used to supply cross sections that exceed 35 mm2.
OTHERS
- Meter by meter marking. (from 10mm2 onwards)
APPLICATIONS
- Domestic use.
- Electrical panel wiring.
- Public places.
CONSTRUCTION PRODUCT REGULATION
- B2ca s1a, d1, a1
National norm / European:
- EN 60332-1 / EN 60332-3
International norm
- IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034
INSTALLATION CONDITIONS
- In conduit.