POWERHARD F RVFV-K AST/DST
Description
For fixed installations that can be vulnerable to mechanical aggression, the POWERHARD F RVFV-K AST/DST cable is particularly well-suited. It is strongly advised for usage in locations (such warehouses, manufacturing companies, and agricultural operations) where rodents may pose a risk to the cable. Its application is also advised for street lighting systems.
Performance of the POWERHARD F RVFV-K AST/DST cable
Electrical functionality
MINIMUM VOLTAGE 0,6/1kV
Typical
UNE 21123-2 and IEC 60502-1
Acceptances
CE/RoHS/VERITAS BUREAU
Regulation of CPR Construction Products
Eca
Thermal efficiency
90ºC is the maximum conductor temperature.
250ºC is the maximum short-circuit temperature (maximum 5 s).
0ºC is the minimum temperature required for handling and installation.
-40ºC is the minimum service temperature for shielded and permanent installations.
Performance of fire
non-propagation of flames according to IEC 60332-1 and EN 60332-1.
decreased emissions of halogen. less than 15% chlorine.
In accordance with EN 50575, the response to fire CPR is Eca.
Performance of mechanical systems
A cable diameter of x10 is the minimum bending radius.
AG4 High severity is the impact resistance rating.
Rat-proof.
Performance of the environment
Resistance to chemicals and oil: Good
The UNE 211605 UV resistance index.
AD7 Immersion is water resistant.
Other
marker from meter to meter.
Conditions of installation
Outside.
buried.
in a conduit.
Uses
industrial use.
Conductor design for the POWERHARD F RVFV-K AST/DST cable
Class 5 (flexible) electrolytic copper, based on EN 60228 and IEC 60228.
Insulation
UNE-HD 603 defines cross-linked polyethylene insulation as type DIX-3, while IEC 60502-1 defines it as type XLPE.
In accordance with HD 308, the standard identifier is:
One Natural
Two x Brown + Blue
3 G Green/yellow + Brown + Blue
Three x Black + Grey + Brown
(reduced cross-section) 3 x + 1 x Brown + Black + Grey + Blue
4 G Green/yellow + Black + Grey + Brown
Four times: Brown, Black, Grey, and Blue
Five grams of brown, black, grey, blue, and green or yellow
Black numbered plus green/yellow for at least 6 G.
Sheath of separation
PVC type ST2 in accordance with IEC 60502-1 and type DMV-18 in accordance with UNE-HD 603 for armor
Double tape armour made of steel or aluminum. Single-core cables use aluminum armor to prevent parasite currents that could cause the cable to overheat. The multicore cables are made of steel tape.
External sheath
Flexible PVC outer sheath, black in color, type DMV18 per UNE-HD 603 and type ST2 per IEC 60502-1.
LOW VOLTAGE 0,6/1kV
UNE-EN 60332-1
Eca
Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
Maximum service temperature: 90ºC.
Maximum conductor temperature: 90ºC.
Maximum conductor temperature: 90ºC.
Industrial use.
Industrial use.
Industral use / Potentially explosion hazard locations. (ATEX)
Industral use / Potentially explosion hazard locations. (ATEX)
Industral use / Potentially explosion hazard locations. (ATEX)
Technology
1. Class 5 (flexible) conductor electrolytic copper, according to EN and IEC 60228.
2. Cross-linked polyethylene (XLPE) insulation.
Insulated conductors are typically identified as follows:
One Natural
Two x Brown + Blue
3 G Green/Yellow + Brown + Blue
Three x Black + Grey + Brown
Black + Grey + Blue + 3 x + 1 x Brown (reduced cross section)
4 G Yellow/green + Black + Grey + Brown
Four times: Brown, Black, Grey, and Blue
Five grams of brown, black, grey, blue, and yellow/green
6 G or more Numbered in black plus yellow or green.
3. PVC separation sheath, type ST2 in accordance with IEC 60502-1 and type DMV-18 in accordance with UNE-HD 603.
4. Armour Double tape armour made of steel or aluminum. Single-core cables use aluminum armor to prevent parasite currents that could cause the cable to overheat. The multicore cables are made of steel tape.
5. Flexible PVC outer sheath, black in color, type DMV-18 in accordance with UNE-HD 603 and type ST2 in accordance with IEC 60502-1.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
- Chemical & Oil resistance: Acceptable.
- UV Resistant: UNE 211605.
- Water resistance: AD7 immersion.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
MECHANICAL PERFORMANCE
- Impact resistance: AG4 High severity.
- Minimum bending radius: x10 cable diameter.
- Rodent proof
FIRE PERFORMANCE
- Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Reaction to fire CPR: Eca, according to EN 50575.
- Reduced halogen emission. Chlorine <15%.
THERMAL PERFORMANCE
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum installation and handling temperature: 0ºC (on cable surface).
- Minimum service temperature: -40ºC (fixed and protected installations)
APPLICATIONS
- Industrial use.
INSTALLATION CONDITIONS
- Buried
- In conduit.
- Open Air.
CONSTRUCTION PRODUCT REGULATION
- Eca
International norm
- IEC 60332-1
APPROVALS
- BUREAU VERITAS
- CE
- RoHS
BASED ON
- IEC 60502-1 – UNE 21123-2
National norm / European:
- UNE-EN 60332-1
OTHERS
- Meter by meter marking.
Reviews