XTREM H07RN-F
Description
Flexible rubber cable, for industrial use.
XTREM® H07RN-F cable performance
Electrical performance
LOW VOLTAGE 450/750 V
Standard
EN 50525-2-21 / IEC 60092-353 / IEC 60245
Approvals
AENOR / HAR / DNV / CE / RoHS
Safe drinking water certificate
Construction Products Regulation (CPR)
Eca
Thermal performance
Maximum conductor temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations) and -25ºC (mobile use)
Fire performance
Flame non-propagation based on EN 60332-1 and IEC 60332-1.
Reaction to fire CPR: Eca, according to EN 50575.
Mechanical performance
Minimum bending radius: 3 x cable diameter (up to 12 mm2). 4 x cable diameter (from 12 mm2 onwards).
Impact resistance: AG2 Medium severity.
Chemical performance
Chemical & Oil resistance: Excellent.
Grease & mineral oils resistance: Excellent.
Water performance
Water resistance: AD8 Submersion.
Cable for submersible pumps in drinkable water based on AS/NZS 4020.
Deep wells
Drinkable water
AWQC.
Other
Meter by meter marking.
Installation conditions
Open Air.
Submersible pumps cable.Applications
Industrial use.
Mobile use.
Robotics.
Wind turbines
Temporary site installations.
Packaging
Available in rolls of 100 m. and drums.
XTREM H07RN-F cable design
Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
Insulation
Rubber (type EI7 according to EN 50363-1).
The standard identification according to HD 308 and EN 50334 is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Yellow/Green
3 x Brown + Black + Grey4 G Brown + Black + Grey + Yellow/Green
4 x Brown + Black + Grey + Blue5 G Brown + Black + Grey + Blue + Yellow/Green
6 or more Black numbered + Yellow/Green
Outer sheath
Flexible rubber, type EM2 according to EN 50363-2-1. Black color.
LOW VOLTAGE 450/750 V
Maximum service temperature: 90ºC.
Industrial use / Mobile use / Robotics / Temporary site installations / Wind turbines
Minimum bending radius: 3 x cable diameter (up to 12 mm2). 4 x cable diameter (from 12 mm2 onwards).
Flame non-propagation based on EN 60332-1 and IEC 60332-1.
UNE-EN 60332-1
Eca
UNE-EN 60332-1
EN 50525-2-21 / IEC 60245
Technology
1. Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
2. Insulation
Rubber (type EI7 according to EN 50363-1).
The standard identification according to HD 308 and EN 50334 is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Yellow/Green
3 x Brown + Black + Grey
4 G Brown + Black + Grey + Yellow/Green
4 x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Blue + Yellow/Green
6 or more Black numbered + Yellow/Green
3. Outer sheath
Flexible rubber, type EM2 according to EN 50363-2-1. Black color.
Cable Specifications
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 450/750 V
MECHANICAL PERFORMANCE
- Impact resistance: AG2 Medium severity.
- Minimum bending radius: 3 x cable Ø (up to 12 mm2). 4 x cable Ø (from 12 mm2 onwards).
WATER PERFORMANCE
- Deep wells
- Drinkable water
- Water resistance: AD8 Submersion.
CHEMICAL PERFORMANCE
- Chemical & Oil resistance: Excellent.
- Grease & mineral oils resistance: Excelente
- UV Resistant based on EN 50618.
FIRE PERFORMANCE
- Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Reaction to fire CPR: Eca, according to EN 50575.
THERMAL PERFORMANCE
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum service temperature: -40ºC (fixed and protected installations) and -25ºC (mobile use)
APPROVALS
- AENOR
- CE
- DNV
- HAR
- RoHS
PACKAGING
- Available in rolls (lengths of 50 and 100 m) and drums.
CONSTRUCTION PRODUCT REGULATION
- Eca
OTHERS
- Meter by meter marking.
APPLICATIONS
- Industrial use.
- Mobile use.
- Robotics.
- Temporary site installations.
- Wind turbines
BASED ON
- EN 50525-2-21.
- IEC 60092-353
- IEC 60245
INSTALLATION CONDITIONS
- Open Air.
- Submersible pumps cable
National norm / European:
- UNE-EN 60332-1
Reviews
There are no reviews yet.