TOPFLEX V-K H05V-K & H07V-K
Description
Because of their intricate layout, TOPFLEX V-K H05V-K and H07V-K cables are specifically made for installations that need flexible cables. This cable is specifically made for wiring in homes. It can also be applied to lighting, cabinets, distributors, and equipment wiring. Installing it beneath false ceilings is also advised.Particularly well-suited for monitoring and signaling installations are cables with a cross section of up to 1 mm2.
Performance of TOPFLEX V-K H05V-K and H07V-K cables
Electrical functionality
300/500 V LOW VOLTAGE
H05V-K (up to 1 mm2): 300/500 V · H07V-K (from 1,5 mm2 onward): 450/750 V.
Typical
IEC 60227-3 and EN 50525-2-31
Acceptances
HAR, AENOR, CE, RoHS, and SEC
Regulation of CPR Construction Products
Eca
Thermal efficiency
70ºC is the maximum conductor temperature.
160ºC is the maximum short-circuit temperature (maximum 5 s).
5ºC is the minimum service temperature.
For protected and fixed installations, the minimum service temperature is -40°C.
Performance of fire
Flame non-propagation according to IEC 60332-1 and EN 60332-1.
Decreased emissions of halogen. less than 15% chlorine.
In accordance with EN 50575, the response to fire CPR is Eca.
Performance of mechanical systems
Five times the cable diameter is the minimum bending radius.
Performance of chemicals
Oil and chemical resistance: Acceptable.
Other
Marking from meter to meter.
Conditions of installation
In a conduit.
Uses
Usage on the go.
Use in the home.
Household appliances.
Installations on temporary sites.
Packing
Available in drums and rolls with lengths of 50 and 100 meters.
Design of TOPFLEX V-K, H05V-K, and H07V-K cables
The conductor
Class 5 (flexible) electrolytic copper, based on EN 60228 and IEC 60228.
Insulation
EN 50363-3 defines extra sliding flexible polyvinyl chloride type TI1.
Insulated conductors are typically identified as follows:
Blue RAL 5012 - Brown RAL 8003 - Black RAL 9005 - Red RAL 3000 - Green/Yellow RAL 6018/1021 - Grey RAL 7000 - Dark Blue RAL 5010 - White RAL 9010 - Orange RAL 2003 - Violet RAL 4005 - Pink RAL 3015
On request, additional colors are available.
LOW VOLTAGE 300/500 V · 450/750 V
Maximum service temperature: 70ºC.
Domestic use / Electrical panel wiring
Flame non-propagation based on EN 60332-1 and IEC 60332-1
UNE-EN 60332-1
UNE-EN 60332-1
Eca
UNE-EN 60332-1
Technology
1. Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
2. Insulation
Extra sliding flexible polyvinyl chloride type TI1 according to EN 50363-3.
The standard identification of insulated conductors is the following:
Blue RAL 5012
Brown RAL 8003
Black RAL 9005
Red RAL 3000
Green/Yellow RAL 6018/1021
Grey RAL 7000
Dark Blue RAL 5010
White RAL 9010
Orange RAL 2003
Violet RAL 4005
Pink RAL 3015
Other colors available on request.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
-
Chemical
Oil resistance: Acceptable.
FIRE PERFORMANCE
- Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Reaction to fire CPR: Eca, according to EN 50575.
- Reduced halogen emission. Chlorine <15%.
MECHANICAL PERFORMANCE
- Minimum bending radius: x5 cable diameter.
ELECTRICAL PERFORMANCE
- Rated Voltage: H05V-K (up to 1 mm2): 300/500 V. H07V-K (from 1,5 mm2 onwards): 450/750 V.
THERMAL PERFORMANCE
- Maximum service temperature: 70ºC.
- Maximum short-circuit temperature: 160ºC (max. 5 s).
- Minimum installation and handling temperature: 5ºC.
- Minimum service temperature: -40ºC (fixed and protected installations)
APPROVALS
- AENOR
- CE
- HAR
- RoHS
- SEC
PACKAGING
- Blue 2,5 mm2 100 m
- BOX COLOUR GUIDE
- Brown 4 mm2 100 m
- COLOUR CROSS SECTION LENGHT (M) PER BOX
- Green 1 mm2 100 m or 200 m
- Grey 6 mm2 100 m
- Red 1,5 mm2 100 m or 200 m
- Small cross sections (from 0,75 mm2 to 6 mm2) are supplied in high resistant colour boxes (see table below). Medium cross sections (from 10 mm2 to 35 mm2) are supplied in 100 m sealed coils. Cross sections > 35 mm2 are supplied in drums.
- Violet 0,75 mm2 100 m
OTHERS
- Meter by meter marking (from 10 mm2 onwards).
APPLICATIONS
- Domestic use.
- Electrical panel wiring.
BASED ON
- EN 50525-2-31 / IEC 60227-3
CONSTRUCTION PRODUCT REGULATION
- Eca
National norm / European:
- EN 60332-1 / EN 60332-3
International norm
- IEC 60332-1
INSTALLATION CONDITIONS
- In conduit.
Reviews