TOXFREE ZH N2XH flex
Description
TOXFREE ZH N2XH flex is a LSHF safety cable for fixed installations. In the event of fire, it does not emit toxic or corrosives gases,preventing any possible harm to people or electronic equipment. For these reasons it is highly recommended for use in public places such as: hospitals, schools, museums, airports, bus terminals, shopping malls, offices, laboratories, etc.
TOXFREE ZH N2XH flex cable performance
Electrical performance
LOW VOLTAGE 0,6/1kV
Standard
IEC 60502-1
Approvals
KEMA KEUR / CE
CPR Construction Product Regulation
B2ca s1a, d1, a1
Thermal performance
Maximum service temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance
Flame non-propagation according to EN 60332-1 and IEC 60332-1.
Fire non-propagation according to EN 60332-3 / IEC 60332-3 and EN 50399.
LSHF (Low Smoke Halogen Free) according to EN 60754-1 and IEC 60754-1.
Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%
Low corrosive gases emission according to EN 60754-2 and IEC 60754-2.
Reaction to fire CPR: B2ca-s1a, d1, a1 or Cca-s1a, d1, a1 according to EN 50575.Mechanical performance
Minimum bending radius: x5 cable diameter.
Impact resistance: AG2 Medium severity.
Environmental performance
Chemical & Oil resistance: Acceptable.
UV Resistant: EN 50618.
Other
Meter by meter marking.
Installation conditions
Open Air.
Buried.
In conduit.
Applications
Industrial use.
Public places.
TOXFREE ZH N2XH flex cable design
Conductor
Electrolytic annealed copper conductor, class 5 (flexible), based on EN 60228 and IEC 60228.
Insulation
Cross-linked polyethylene (XLPE) insulation according to IEC 60502-1.
The standard identification of insulated conductors according to HD 308 is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Green/Yellow
3 x Brown + Black + Grey
3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)
4 G Brown + Black + Grey + Green/Yellow
4 x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Blue + Green/Yellow
Outer sheath
Low Smoke Zero Halogen (LSZH) polyolefin. Black colour.
KEMA KEUR / CE & RoHS
Chemical & Oil resistance: Acceptable
Water resistance: AD5 Jets
IEC 60502-1
Impact resistance: AG2 Medium severity
Technology
1. Conductor
Electrolytic annealed copper conductor, class 5 (flexible), based on EN 60228 and IEC 60228.
2. Insulation
Cross-linked polyethylene (XLPE) according to IEC 60502-1.
The standard identification of insulated conductors according to HD 308 is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Yellow/green
3 x Brown + Black + Grey
3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)
4 G Brown + Black + Grey + Yellow/green
4 x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Blue + Yellow/green
3. Outer sheath
Low Smoke Halogen Free (LSHF) polyolefin. Black colour.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
- Chemical & Oil resistance: Acceptable.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
MECHANICAL PERFORMANCE
- Impact resistance: AG2 Medium severity.
- Minimum bending radius: x5 cable diameter.
WATER RESISTANCE
- Water resistance: AD8 Submersion.
CHEMICAL PERFORMANCE
- UV Resistant based on EN 50618.
FIRE PERFORMANCE
- Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.
- Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
- Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.
- Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.
THERMAL PERFORMANCE
- Impact resistance: AG2 Medium severity.
- Minimum bending radius: x5 cable diameter.
APPROVALS
- CE
- KEMA KEUR
INSTALLATION CONDITIONS
- Buried
- In conduit.
- Open Air.
National norm / European:
- UNE-EN 60332-1
CONSTRUCTION PRODUCT REGULATION
- B2ca s1a, d1, a1
BASED ON
- IEC 60502-1
International norm
- IEC 60502-1
OTHERS
- Meter by meter marking.