XTREM H07RN-F
Description
Flexible rubber cable, for industrial use.
Low voltage appliances, such as electric motors and submersible pumps in deep water installations, as well as numerous other electrical devices, can be powered by Xtrem® H07RN-F rubber cables. The Xtrem® H07RN-F cable's exceptional mechanical strength and flexibility make it perfect for power transmission in both fixed installations and mobile services. According to HD 516, the insulating material's excellent dielectric qualities allow the nominal voltage to reach 1000 V. The Top Cable All kinds of electrical equipment, including motors and submersible pumps in deep water installations, can be powered using Xtrem® H07RN-F cables (AD8).
Performance of the XTREM® H07RN-F cable
Electrical functionality
LOW V (450/750 V)
Typical
IEC 60092-353, EN 50525-2-21, and IEC 60245
Acceptances
HAR, DNV, CE, RoHS, AENOR
Certificate of safe drinking water
Regulation of Construction Products (CPR)
Eca
Thermal efficiency
90ºC is the maximum conductor temperature.
250ºC is the maximum short-circuit temperature (maximum 5 s).
For fixed and shielded installations, the minimum service temperature is -40°C; for mobile use, it is -25°C.
Performance of fire
non-propagation of flames according to IEC 60332-1 and EN 60332-1.
In accordance with EN 50575, the response to fire CPR is Eca.
Performance of mechanical systems
Three times the cable diameter (up to 12 mm2) is the minimum bending radius. 4 times wire diameter (starting at 12 mm2).
Medium severity AG2 impact resistance.
Performance of chemicals
Excellent resistance to chemicals and oil.
Excellent resistance to mineral and grease oils.
Performance of water
Resistance to water: AD8 Submersion.
AS/NZS 4020-based cable for submersible pumps in potable water.
Wells that are deep
Potable water
AWQC.
Other
marker from meter to meter.
Conditions of installation
Outside.
Cable for submersible pumps: Uses
industrial use.
usage on the go.
robotics.
Windmills
installations on temporary sites.
Packing
Available in drums and 100-meter rolls.
Design of the XTREM H07RN-F cable conductor
Class 5 (flexible) electrolytic copper, based on EN 60228 and IEC 60228.
Insulation
EI7 rubber, as defined by EN 50363-1.
The following is the standard identification as per HD 308 and EN 50334:
One Natural
Two x Brown + Blue
3 G Yellow/Green + Brown + Blue
Three x Black + Grey + Brown
4 G Yellow/Green + Black + Grey + Brown
Four times: Brown, Black, Grey, and Blue
Five grams of brown, black, grey, blue, and yellow/green
Six or more black numbers plus green or yellow
External sheath
Flexible rubber, black in color, type EM2 per EN 50363-2-1.
LOW VOLTAGE 450/750 V
Maximum service temperature: 90ºC.
Industrial use / Mobile use / Robotics / Temporary site installations / Wind turbines
Minimum bending radius: 3 x cable diameter (up to 12 mm2). 4 x cable diameter (from 12 mm2 onwards).
Flame non-propagation based on EN 60332-1 and IEC 60332-1.
UNE-EN 60332-1
Eca
UNE-EN 60332-1
EN 50525-2-21 / IEC 60245
Technology
1. Class 5 (flexible) conductor electrolytic copper, according to EN and IEC 60228.
2. Rubber insulation (type EI7 per EN 50363-1).
The following is the standard identification as per HD 308 and EN 50334:
One Natural
Two x Brown + Blue
3 G Yellow/Green + Brown + Blue
Three x Black + Grey + Brown
4 G Yellow/Green + Black + Grey + Brown
Four times: Brown, Black, Grey, and Blue
Five grams of brown, black, grey, blue, and yellow/green
Six or more black numbers plus green or yellow
3. The outer sheath:
Flexible rubber, black in color, type EM2 per EN 50363-2-1.
Cable Specifications
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 450/750 V
MECHANICAL PERFORMANCE
- Impact resistance: AG2 Medium severity.
- Minimum bending radius: 3 x cable Ø (up to 12 mm2). 4 x cable Ø (from 12 mm2 onwards).
WATER PERFORMANCE
- Deep wells
- Drinkable water
- Water resistance: AD8 Submersion.
CHEMICAL PERFORMANCE
- Chemical & Oil resistance: Excellent.
- Grease & mineral oils resistance: Excelente
- UV Resistant based on EN 50618.
FIRE PERFORMANCE
- Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Reaction to fire CPR: Eca, according to EN 50575.
THERMAL PERFORMANCE
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum service temperature: -40ºC (fixed and protected installations) and -25ºC (mobile use)
APPROVALS
- AENOR
- CE
- DNV
- HAR
- RoHS
PACKAGING
- Available in rolls (lengths of 50 and 100 m) and drums.
CONSTRUCTION PRODUCT REGULATION
- Eca
OTHERS
- Meter by meter marking.
APPLICATIONS
- Industrial use.
- Mobile use.
- Robotics.
- Temporary site installations.
- Wind turbines
BASED ON
- EN 50525-2-21.
- IEC 60092-353
- IEC 60245
INSTALLATION CONDITIONS
- Open Air.
- Submersible pumps cable
National norm / European:
- UNE-EN 60332-1

Reviews
There are no reviews yet.