TOXFREE ZH XTREM H07ZZ-F (AS)
Description
The extra-flexible LSZH rubber cable for mobile service.
TOXFREE ZH Xtrem H07ZZ-F (AS) is a flexible cable for mobile service, suitable for installations where low smoke and halogen free fumes under fire conditions are required. Suitable for installations where the cable must withstand medium mechanical stress, for machines in industrial and agricultural workshops, for motors and transportable machines on construction sites, for windmills and for agricultural applications.
TOXFREE ZH XTREM H07ZZ-F (AS) cable performance
Electrical performance
LOW VOLTAGE 450/750 V
Standard
EN 50525-3-21
Standards and approvals
AENOR / HAR / CE / UKCA
Construction Products Regulation (CPR)
B2ca-s2b, d1, a1 (according to cross-section)
Thermal performance
Maximum conductor temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance
Flame non-propagation based on EN 60332-1 and IEC 60332-1.
Fire non-propagation based on EN 60332-3 and IEC 60332-3.
Low smoke emission based on EN 61034 and IEC 61034: Light transmittance > 60%
Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
Halogen free according to EN 60754-1 / IEC 60754-1.
Reaction to fire CPR: B2ca-s1b, d1, a1 or Cca-s1b, d2, a1 according to EN 50575.
Mechanical performance
Minimum bending radius: 3x cable diameter <12 mm. 4x cable diameter≥12 mm.
Impact resistance: AG2 Medium severity.
Chemical performance
Chemical & Oil resistance: Excellent.
Grease & mineral oils resistance: Excellent.
Water performance
Water resistance: AD7 Immersion.
Other
Meter by meter marking.
Installation conditions
Open Air.
In conduit.
Applications
Industrial use.
Mobile use.
Wind turbines.
TOXFREE ZH XTREM H07ZZ-F (AS) cable design
Conductor
Electrolytic annealed copper, class 5 (flexible), based on EN 60228 and IEC 60228.
Insulation
LSHF Rubber type EI8 according to EN 50363- 5.
The standard identification of insulated conductors is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Yellow/Green
4 G Brown + Black + Grey + Yellow/Green
5 G Brown + Black + Grey + Blue + Yellow/Green
6 or more Black numbered + Yellow/Green
Outer sheath
Low Smoke halogen free (LSHF) rubber type EM8 according to EN 50363-6. Black color.
LOW VOLTAGE 450/750 V
Maximum service temperature: 90ºC.
Industrial use. / Mobile use / Wind turbines
Low smoke emission according to EN 61034 and IEC 61034.: Light transmittance > 60%
AENOR / HAR / CE / UKCA
Cca s1b, d2,a1
Technology
1. Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
2. Insulation
LSHF Rubber.
The standard identification of insulated conductors is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Yellow/Green
4 G Brown + Black + Grey + Yellow/Green
5 G Brown + Black + Grey + Blue + Yellow/Green
6 or more Black numbered + Yellow/Green
3. Outer sheath
Low Smoke halogen free (LSHF) rubber type EM8 according to EN 50363-6. Black color.
Cable Specifications
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 450/750 V
MECHANICAL PERFORMANCE
- Impact resistance: AG2 Medium severity.
- Minimum bending radius: x3 cable diameter.
WATER PERFORMANCE
- Water resistance: AD7 Immersion
CHEMICAL PERFORMANCE
- Chemical & Oil resistance: Excellent.
- Grease & mineral oils resistance: Excelent.
FIRE PERFORMANCE
- Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.
- Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Halogen free based on EN 60754-1
- Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
- Low smoke emission according to EN 61034 and IEC 61034.: Light transmittance > 60%
- Reaction to fire CPR: B2ca-s1b, d1, a1 / Cca-s1b, d2, a1 according to EN 50575
THERMAL PERFORMANCE
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum service temperature: -40ºC (fixed and protected installations)
APPROVALS
- AENOR
- CE
- RoHS
- UKCA
CONSTRUCTION PRODUCT REGULATION
- B2ca s1a, d1, a1
OTHERS
- Meter by meter marking.
APPLICATIONS
- Industrial use.
- Mobile use.
- Wind turbines
BASED ON
- UNE-EN 50525-3-21
INSTALLATION CONDITIONS
- Open Air.
- Submersible pumps cable
National norm / European:
- UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034
International norm
- IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034
Reviews