TOXFREE ZH RZ1FZ1-K (AS)
Description
LOW VOLTAGE 0,6/1kV
Maximum service temperature: 90ºC
lame non-propagation based on EN 60332-1 and IEC 60332-1
Industrial use
IEC 60502-1 / UNE 21123-4
Technology
1. Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
2. Insulation
Cross-linked polyethylene (XLPE).
The standard identification of insulated conductors is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Yellow/green
3 x Brown+ Black+ Grey
4 G Brown + Black + Grey + Yellow/green
4 x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Blue + Yellow/green
6 or more Black numbered + Green/yellow
3. Armour bedding
Low smoke zero halogen (LSZH) polyolefin inner sheath.
4. Armour
Double steel or aluminium tape armour. Aluminium armour is used in single-core cables to avoid parasite currents that may overheat the cable. Steel tape is used in the multicore cables.
5. Outer sheath
Low Smoke Zero Halogen (LSZH) polyolefin type ST8 according to IEC 60502-1 and type DMZ-E according to UNE 21123-4. Green color, non-toxic and fire retardant.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
- Chemical & Oil resistance: Acceptable.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
MECHANICAL PERFORMANCE
- Impact resistance: AG4 High severity.
- Minimum bending radius: x10 cable diameter.
- Rodent proof
WATER PERFORMANCE
- Water resistance: AD5 Jets.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
FIRE PERFORMANCE
- Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399
- Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Low corrosive gases emission according to IEC 60754-2
- Low smoke emission according to EN 61034 and IEC 61034.: Light transmittance > 60%
- Low smoke halogen free according to IEC 60754-1
- Reaction to fire CPR: Cca-s1b, d2, a1 according to EN 50575.
THERMAL PERFORMANCE
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum service temperature: -40ºC (fixed and protected installations)
CHEMICAL PERFORMANCE
- UV Resistant based on EN 50618.
APPROVALS
- CE
- RoHS
INSTALLATION CONDITIONS
- Buried.
- In conduit.
- Open Air.
APPLICATIONS
- Industrial use.
International norm
- IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034
CONSTRUCTION PRODUCT REGULATION
- Cca s1a, d1, a1
BASED ON
- IEC 60502-1 / UNE 21123-4
National norm / European:
- EN 60332-1 / EN 60332-3 / EN 50267-1 / EN 50267-2 / EN 61034
OTHERS
- Meter by meter marking.