TOXFREE ZH RZ1 (AS) AL
Description
TOXFREE ZH RZ1 (AS) AL is an aluminium LSHF cable for fixed installations. In the event of fire, it does not emit toxic gases, nor does it give off corrosive gases, avoiding any possible damage to people or electronic equipment. These cables are especially recommended for installation in public places and in installations where safety is a priority.
TOXFREE ZH RZ1 (AS) AL cable performance
Electrical performance
LOW VOLTAGE 0,6/1kV
Standard
IEC 60502-1 / UNE 21123-4
Approvals
CE / RoHS
CPR Construction Products Regulation
B2ca s1a, d1, a1, or B2ca s1b, d1, a1Thermal performance
Maximum conductor temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance
Flame non-propagation based on EN 60332-1 and IEC 60332-1.
Fire non-propagation based on EN 60332-3 / IEC 60332-3 and EN 50399.
LSHF (Low Smoke Halogen Free) based on EN 60754-1 and IEC 60754-1.
Low smoke emission based on EN 61034 and IEC 61034: Light transmittance > 80%
Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
Reaction to fire CPR: B2ca s1a, d1, a1, or Cca-s1a, d1, a1 according to EN 50575.Mechanical performance
Minimum bending radius: x 5 cable diameter.
Impact resistance: AG2 Medium severity.
Chemical performance
Chemical & Oil resistance: Acceptable.
UV Resistant according to EN 50618.
Water performance
Water resistance: AD8 Submersion.
Other
Meter by meter marking.
Installation conditions
Open Air.
Buried.
In conduit.
Applications
Industrial use.
Public places.
TOXFREE ZH RZ1 (AS) AL cable design
Conductor
Aluminium, class 2, based on N 60228 and IEC 60228.
Insulation
Cross-linked polyethylene (XLPE) according to IEC 60502-1 and type DIX-3 according to HD 603.
Low Smoke Halogen Free (LSHF) polyolefin type ST8 according to IEC 60502- 1 and type DMZ-E according to UNE 21123-4. Green color.
LOW VOLTAGE 0,6/1kV
UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034
Maximum service temperature: 90ºC.
Industrial use / Public places.
Technology
Conductor
Aliuminium, class 2, based on UNE-EN 60228 and IEC 60228.
Insulation
Cross-linked polyethylene (XLPE).
The standard identification of insulated conductors according to HD 308 is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Green/Yellow
3 x Brown + Black + Grey
3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)
4 G Brown + Black + Grey + Green/Yellow
4x Brown+Black+Grey+Blue
5 G Brown + Black + Grey + Blue + Green/Yellow
6 or more Black numbered + Green/Yellow
Outer sheath
Low Smoke Zero Halogen (LSZH) polyolefin type ST8 according to IEC 60502- 1 and type DMZ-E according to UNE 21123-4. Green color.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
-
Chemical
Oil resistance: Acceptable.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
MECHANICAL PERFORMANCE
-
Impact resistance: AG2
Medium severity. -
Minimum bending radius:
x5 cable diameter.
WATER RESISTANCE
- Water resistance: AD8 Submersion.
CHEMICAL PERFORMANCE
- UV Resistant: based on UNE 211605.
FIRE PERFORMANCE
-
Fire non-propagation based on
EN 60332-3 / IEC 60332-3
/ EN 50399. - Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Low corrosive gases emission according to IEC 60754-2
-
Low smoke emission according
to EN 61034 and IEC 61034: Light transmittance > 80%. - Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.
- Reaction to fire CPR: Cca-s1a, d1, a1, based on EN 50575.
THERMAL PERFORMANCE
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum service temperature: -40ºC (fixed and protected installations)
APPROVALS
- AENOR
- CE
- KEMA KEUR
- RoHS
- SEC
- UKCA
BASED ON
- IEC 60502-1 / UNE 21123-4
National norm / European:
- UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034
APPROVALS
- Industrial use.
- Public places.
CONSTRUCTION PRODUCT REGULATION
- B2ca s1a, d1, a1
- B2ca s1b, d1, a1
INSTALLATION CONDITIONS
- Buried
- In conduit.
- Open Air.
International norm
- IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034
OTHERS
- Meter by meter marking.