POWERFLEX RV-K
Description
TOXFREE ZH YMz1Kf is a LSHF safety cable. In the event of fire, it does not emit toxic gases, nor does it give off corrosive gases, avoiding any possible damage to people or electronic equipment. For these reasons it is highly recommended for use in public places such as: hospitals, schools, museums, airports, bus terminals, shopping malls, offices, laboratories, etc.
TOXFREE ZH YMz1Kf cable performance
Electrical performance
LOW VOLTAGE 0,6/1kV
Standard
IEC 60502-1 / UNE 21123-4
Approvals
AENOR / SEC / KEMA KEUR / CE / RoHS
CPR (Construction Product Regulation)
B2ca s1a, d1, a1 or Cca s1a, d1, a1 (according to cross-section)
Thermal performance
Maximum conductor temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Minimum installation and handling temperature: -0ºC.
Fire performance
Flame non-propagation according to EN 60332-1/IEC 60332-1.
Fire non-propagation according to EN 60332-3/IEC 60332-3 and EN 50399.
LSHF (Low Smoke Halogen Free) based on EN 60754-1/IEC 60754-1.
Low smoke emission based on UNE-EN 61034 and IEC 61034: Light transmittance > 80%.
Low corrosive gases emission based on EN 60754-2/IEC 60754-2.
Reaction to fire CPR: B2ca s1a, d1, a1 or Cca s1a, d1, a1 (see cross-section), according to EN 50575.
Mechanical performance
Minimum bending radius: x5 cable diameter.
Impact resistance: AG2 Medium severity.
Environmental performance
Chemical & Oil resistance: Acceptable.
UV Resistant according to EN 50618.
Water resistance: AD8 Submersion.
Other
Meter by meter marking.
Installation conditions
Open Air.
Buried.
In conduit.
Applications
Industrial use.
Public places.
Packaging
Available in rolls (lengths of 100 m) and drums.
TOXFREE ZH YMz1Kf cable design
Conductor
Electrolytic annealed copper conductor, class 5 (flexible), according to EN 60228 and IEC 60228.
Insulation
Cross-linked polyethylene type XLPE according to IEC 60502-1 and type DIX-3 according to HD 603. The standard identification of insulated conductors according to HD 308 is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Green/Yellow
3 x Brown + Black + Grey
3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)
4 G Brown + Black + Grey + Green/Yellow
4 x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Blue + Green/Yellow
6 G or more Black numbered + Green/Yellow
Outer sheath
Low Smoke Halogen Free (LSHF) polyolefin outer sheath, type ST8 according to IEC 60502- 1 and type DMZ-E according to UNE 21123-4. Green color.
LOW VOLTAGE 0,6/1kV
Maximum conductor temperature: 90ºC.
Water resistance: AD5 Jets
Flame non-propagation based on EN 60332-1 and IEC 60332-1
Industrial use / Public places.
Technology
1. Conductor
Electrolytic annealed copper conductor, class 5 (flexible), based on EN 60228 and IEC 60228.
2. Insulation
Cross-linked polyethylene (XLPE) according to IEC 60502-1.
The standard identification of insulated conductors according to HD 308 is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Yellow/green
3 x Brown + Black + Grey
3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)
4 G Brown + Black + Grey + Yellow/green
4 x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Blue + Yellow/green
3. Outer sheath
Low Smoke Halogen Free (LSHF) polyolefin. Black colour.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
-
Chemical
Oil resistance: Acceptable.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
MECHANICAL PERFORMANCE
-
Impact resistance: AG2
Medium severity. -
Minimum bending radius:
x5 cable diameter.
WATER RESISTANCE
- Water resistance: AD8 Submersion.
CHEMICAL PERFORMANCE
- UV Resistant based on EN 50618.
FIRE PERFORMANCE
-
Fire non-propagation based on
EN 60332-3 / IEC 60332-3
/ EN 50399. - Flame non-propagation based on EN 60332-1 and IEC 60332-1
-
Low corrosive gases emission
based on UNE-EN 60754-2 and IEC 60754-2. -
Low smoke emission according
to EN 61034 and IEC 61034: Light transmittance > 80%.
THERMAL PERFORMANCE
-
Impact resistance: AG2 Medium
severity. -
Minimum bending radius: x5
cable diameter.
APPROVALS
- CE
- KEMA KEUR
INSTALLATION CONDITIONS
- Buried
- In conduit.
- Open Air.
National norm / European:
- UNE-EN 60332-1
CONSTRUCTION PRODUCT REGULATION
- B2ca s1a, d1, a1
BASED ON
- IEC 60502-1
International norm
- IEC 60502-1
OTHERS
- Meter by meter marking.
Reviews