Description
The TOXFREE ZH YMz1Kf safety cable is LSHF. It doesn't release corrosive or hazardous gasses in the case of a fire, protecting humans and electronic devices from potential harm. It is therefore strongly advised for usage in public settings like hospitals, schools, museums, bus terminals, airports, shopping centers, offices, labs, etc.
Performance of the TOXFREE ZH YMz1Kf cable
Electrical functionality
MINIMUM VOLTAGE 0,6/1kV
Typical
UNE 21123-4 and IEC 60502-1
Acceptances
CE, RoHS, AENOR, SEC, and KEMA KEUR
Regulation of Construction Products, or CPR
Depending on the cross-section, B2ca s1a, d1, a1 or Cca s1a, d1, a1
Thermal efficiency
90ºC is the maximum conductor temperature.
250ºC is the maximum short-circuit temperature (maximum 5 s).
-40ºC is the minimum service temperature for shielded and permanent installations.
-0ºC is the minimum temperature required for handling and installation.
Performance of fire
According to EN 60332-1/IEC 60332-1, flames do not spread.
In accordance with EN 60332-3/IEC 60332-3 and EN 50399, fire does not spread.
Low Smoke Halogen Free, or LSHF, is as defined by EN 60754-1/IEC 60754-1.
According to UNE-EN 61034 and IEC 61034, low smoke emission is defined as light transmittance > 80%.
low emissions of corrosive gases in accordance with EN 60754-2/IEC 60754-2.
In accordance with EN 50575, the response to fire CPR is either B2ca s1a, d1, a1 or Cca s1a, d1, a1 (see cross-section).
Performance of mechanical systems
A minimum cable diameter of x5 is required for bending.
Medium severity AG2 impact resistance.
Performance of the environment
Resistance to chemicals and oil: Acceptable.
In accordance with EN 50618, UV resistant.
Resistance to water: AD8 Submersion.
Other
marker from meter to meter.
Conditions of installation
Outside.
buried.
in a conduit.
Uses
industrial use.
public areas.
Packing
available in drums and rolls (100 m in length).
Design of TOXFREE ZH YMz1Kf wire conductor
Class 5 (flexible) electrolytic annealed copper conductor in accordance with EN and IEC 60228.
Insulation
IEC 60502-1 classifies cross-linked polyethylene as type XLPE, while HD 603 classifies it as type DIX-3. In accordance with HD 308, insulated conductors are typically identified as follows:
One Natural
Brown + 2 x Blue
3 G Green/Yellow + Brown + Blue
Three times: Brown, Black, and Grey
(reduced cross-section) 3 x + 1 x Brown + Black + Grey + Blue
Four grams of brown, black, grey, and green or yellow
Four times: Brown, Black, Grey, and Blue
5 G Green/Yellow + Brown + Black + Grey + Blue
6 G or more Black digits plus green/yellow
External sheath
Polyolefin outer sheath for Low Smoke Halogen Free (LSHF), type ST8 in accordance with IEC 60502- 1 and type DMZ-E in accordance with UNE 21123-
Flame non-propagation based on EN 60332-1 and IEC 60332-1
Maximum conductor temperature: 90ºC.
B2ca s1a, d1, a1 |||| Cca s1a, d1, a1
Industrial use / Public places.
LOW VOLTAGE 0,6/1kV
AENOR / SEC / KEMA KEUR / CE / RoHS
UV Resistant: based on UNE 211605.
Technology
1. Conductor
Electrolytic annealed copper conductor class 5 (flexible) according to EN 60228 and IEC 60228.
2. Insulation
Special low smoke and halogen free polyolefin insulation.
The standard identification of insulated conductors according to HD 308 is the following:
6G or more Black numbered + Green/Yellow
3. Outer sheath
Low Smoke Halogen Free (LSHF) polyolefin outer sheath, not toxic and fire retardant. Green colour. Other outer sheath colours available on request.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
- Chemical & Oil resistance: Acceptable.
- UV Resistant according to EN 50618.
- Water resistance: AD8 Submersion.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
MECHANICAL PERFORMANCE
- Impact resistance: AG2 Medium severity.
- Minimum bending radius: x5 cable diameter.
WATER RESISTANCE
- Water resistance: AD8 Submersion.
CHEMICAL PERFORMANCE
- UV Resistant: based on UNE 211605.
FIRE PERFORMANCE
- Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.
- Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Low corrosive gases emission according to IEC 60754-2
- Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.
- LSHF (Low Smoke Halogen Free) based on UNE-EN 60754-1 and IEC 60754-1.
- Reaction to fire CPR: Cca-s1a, d1, a1, based on EN 50575.
THERMAL PERFORMANCE
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum service temperature: -40ºC (fixed and protected installations)
APPROVALS
- AENOR
- KEMA KEUR
- CE
- RoHS
INSTALLATION CONDITIONS
- Buried
- In conduit.
- Open Air.
APPLICATIONS
- Industrial use.
- Public places.
OTHERS
- Meter by meter marking.
CONSTRUCTION PRODUCT REGULATION
- B2ca s1a, d1, a1
- Cca s1a, d1, a1
BASED ON
- EN 60228 / IEC 60228
- IEC 60502-1 – UNE 21123-2
PACKAGING
- Available in rolls (lengths of 50 and 100 m) and drums.
International norm
- IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034