POWERHARD M RVhMVh-K AWA/SWA
Description
Street lighting, agricultural facilities, production plants, and other sites where the cable is exposed to high mechanical aggression can all use POWERHARD M RVhMVh-K AWA/SWA cable.
A version of this cable that is resistant to hydrocarbons is also offered.
Performance of the POWERHARD M RVhMVh-K AWA/SWA cable
Electrical functionality
MINIMUM VOLTAGE 0,6/1kV
Typical
IEC 60502-1
Acceptances
CE/RoHS/VERITAS BUREAU
Regulation of CPR Construction Products
Eca
Thermal efficiency
90ºC is the maximum conductor temperature.
250ºC is the maximum short-circuit temperature (maximum 5 s).
-40ºC is the minimum service temperature for shielded and permanent installations.
0°C is the minimum temperature required for handling and installation (on cable surface).
Performance of fire
In accordance with EN 50575, the response to fire CPR is Eca.
Reduced halogen emission. less than 15% chlorine.
Performance of mechanical systems
A cable diameter of x10 is the minimum bending radius.
AG4 High severity is the impact resistance rating.
Rat-proof.
Performance of the environment
Good resistance to chemicals and oil.
The UNE 211605 UV resistance index.
AD7 Immersion is water resistant.
Other
Meter by meter marking.
Conditions of installation
Outside.
buried.
in a conduit.
Uses
industrial use.
Conductor design for POWERHARD M RVhMVh-K AWA/SWA cables
Class 5 (flexible) electrolytic copper, based on EN 60228 and IEC 60228.
Insulation
insulator made of cross-linked polyethylene type XLPE in accordance with IEC 60502-1 and DIX-3 in accordance with HD 603.
In accordance with HD 308, insulated conductors are typically identified as follows:
One Natural
Two x Brown + Blue
3 G Green/yellow + Brown + Blue
Three x Black + Grey + Brown
(reduced cross section) 3 x + 1 x Brown + Black + Grey + Blue
4 G Green/yellow + Black + Grey + Brown
Four times: Brown, Black, Grey, and Blue
5 G Brown + Black + Grey + Blue + Green/yellow
6 G or more Brown + Black numbered + Green/Yellow
Inner covering
PVC.
Armor
Galvanized steel wire armour. Single-core cables use aluminum armor to prevent parasite currents that could cause the cable to overheat.
Outer sheath
PVC outer sheath type ST2 according to IEC 60502-1. Black color.
LOW VOLTAGE 0,6/1kV
EN 60332-1
Eca
Flame non-propagation based on EN 60332-1 and IEC 60332-1.
Maximum service temperature: 90ºC.
Industrial use
Technology
1. Class 5 (flexible) conductor electrolytic copper, according to EN and IEC 60228.
2. Cross-linked polyethylene (XLPE) insulation.
Insulated conductors are typically identified as follows:
One natural
Two x Brown + Blue
3 G Green/Yellow + Brown + Blue
Three x Black + Grey + Brown
Black + Grey + Blue + 3 x + 1 x Brown (reduced cross-section)
4 G Green/Yellow + Black + Grey + Brown
Four times: Brown, Black, Grey, and Blue
Five grams of brown, black, grey, blue, and green or yellow
Six G or more conductors: Green/Yellow + Black numbered.
3. PVC inner covering.
4. Armour Armour made of galvanized steel wire. Single-core cables use aluminum armor to prevent parasite currents that could cause the cable to overheat.
5. PVC outer sheath type ST2, which is black in color and complies with IEC 60502-1.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
- Chemical & Oil resistance: Good.
- UV Resistant: UNE 211605.
- Chemical & Oil resistance: Good.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
MECHANICAL PERFORMANCE
- Impact resistance: AG4 High severity.
- Minimum bending radius: x10 cable diameter.
- Rodent proof
WATER RESISTANCE
- Water resistance: AD7 Immersion
FIRE PERFORMANCE
- Reaction to fire CPR: Eca, according to EN 50575.
- Reduced halogen emission. Chlorine <15%.
THERMAL PERFORMANCE
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum installation and handling temperature: 0ºC (on cable surface).
- Minimum service temperature: -40ºC (fixed and protected installations)
APPLICATIONS
- Industrial use.
INSTALLATION CONDITIONS
- Buried
- In conduit.
- Open Air.
CONSTRUCTION PRODUCT REGULATION
- Eca
International norm
- IEC 60502-1
APPROVALS
- BUREAU VERITAS
- CE
- RoHS
BASED ON
- IEC 60502-1
OTHERS
- Meter by meter marking.
Reviews