TOXFREE ZH XTREM H07ZZ-F (AS)
Description
The extra-flexible LSZH rubber cable for mobile service.
A flexible mobile service cable called TOXFREE ZH Xtrem H07ZZ-F (AS) is appropriate for installations that need to emit halogen-free fumes and minimal smoke during a fire. Ideal for windmills, agricultural applications, motors and portable machinery on construction sites, machines in industrial and agricultural workshops, and installations where the cable must sustain medium mechanical stress.
Performance of the TOXFREE ZH XTREM H07ZZ-F (AS) cable
Electrical functionality
450/750 V LOW VOLTAGE
Typical
EN 50525-3-21
Approvals and standards
HAR, CE, UKCA, and AENOR
Regulation of Construction Products (CPR)
B2ca-s2b, d1, a1 (based on cross-section)
Thermal efficiency
90ºC is the maximum conductor temperature.
250ºC is the maximum short-circuit temperature (maximum 5 s).
For protected and fixed installations, the minimum service temperature is -40ºC.
Performance of fire
flame non-propagation according to IEC 60332-1 and EN 60332-1.
Fire non-propagation according to IEC 60332-3 and EN 60332-3.
Low smoke emissions according to IEC 61034 and EN 61034: Transmittance of light > 60%
low emissions of corrosive gases in accordance with IEC 60754-2 and UNE-EN 60754-2.
According to EN 60754-1 and IEC 60754-1, halogen is free. According to EN 50575, the response to fire CPR is either B2ca-s1b, d1, a1 or Cca-s1b, d2, a1.
Performance of mechanical systems
3x cable diameter <12 mm is the minimum bending radius. Four cables with a diameter of 12 mm or more.
AG2 Medium severity impact resistance.
Performance of chemicals
Excellent resistance to chemicals and oil.
Excellent resistance to mineral and grease oils.
Performance of water
AD7 Immersion is water resistant.
Other
marking from meter to meter.
Conditions of installation
Outside.
in a conduit.
Uses
industrial application.
usage on the go.
windmills.
Cable design conductor for TOXFREE ZH XTREM H07ZZ-F (AS)
Class 5 (flexible) electrolytically annealed copper, according to EN 60228 and IEC 60228.
Conductor:
Electrolytic annealed copper, class 5 (flexible), based on EN 60228 and IEC 60228.
Insulation
LSHF Rubber type EI8 in accordance with EN 50363-5.
Insulated conductors are typically identified as follows:
One Natural
Two x Brown + Blue
3 G Yellow/Green + Brown + Blue
4 G Brown + Black + Grey + Green/Yellow
5 G Brown + Black + Grey + Blue + Green/Yellow
Six or more black numbers plus yellow or green
External sheath
Black, Low Smoke Halogen Free (LSHF) rubber type EM8 in accordance with EN 50363-6.
LOW VOLTAGE 450/750 V
Maximum service temperature: 90ºC.
Industrial use. / Mobile use / Wind turbines
Low smoke emission according to EN 61034 and IEC 61034.: Light transmittance > 60%
AENOR / HAR / CE / UKCA
Cca s1b, d2,a1
Technology
1. Conductor
Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
2. Insulation
LSHF Rubber.
The standard identification of insulated conductors is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Yellow/Green
4 G Brown + Black + Grey + Yellow/Green
5 G Brown + Black + Grey + Blue + Yellow/Green
6 or more Black numbered + Yellow/Green
3. Outer sheath:
Low Smoke halogen free (LSHF) rubber type EM8 according to EN 50363-6. Black color.
Cable Specifications
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 450/750 V
MECHANICAL PERFORMANCE
- Impact resistance: AG2 Medium severity.
- Minimum bending radius: x3 cable diameter.
WATER PERFORMANCE
- Water resistance: AD7 Immersion
CHEMICAL PERFORMANCE
- Chemical & Oil resistance: Excellent.
- Grease & mineral oils resistance: Excelent.
FIRE PERFORMANCE
- Fire non-propagation based on EN 60332-3 / IEC 60332-3 / EN 50399.
- Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Halogen free based on EN 60754-1
- Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
- Low smoke emission according to EN 61034 and IEC 61034.: Light transmittance > 60%
- Reaction to fire CPR: B2ca-s1b, d1, a1 / Cca-s1b, d2, a1 according to EN 50575
THERMAL PERFORMANCE
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum service temperature: -40ºC (fixed and protected installations)
APPROVALS
- AENOR
- CE
- RoHS
- UKCA
CONSTRUCTION PRODUCT REGULATION
- B2ca s1a, d1, a1
OTHERS
- Meter by meter marking.
APPLICATIONS
- Industrial use.
- Mobile use.
- Wind turbines
BASED ON
- UNE-EN 50525-3-21
INSTALLATION CONDITIONS
- Open Air.
- Submersible pumps cable
National norm / European:
- UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034
International norm
- IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034