TOXFREE ZH RZ1 (AS) AL
Description
An aluminum LSHF cable for permanent installations is called TOXFREE ZH RZ1 (AS) AL. It doesn't release corrosive or toxic gases in the event of a fire, protecting people and electronic devices from potential harm. These cables are particularly advised for use in installations where safety is a top concern as well as in public areas.
Performance of the TOXFREE ZH RZ1 (AS) AL cable
Electrical functionality
MINIMUM VOLTAGE 0,6/1kV
Typical
UNE 21123-4 and IEC 60502-1
Acceptances
RoHS and CE
Regulation of CPR Construction Products
either B2ca s1a, d1, a1, or B2ca s1b, d1, a1
Thermal efficiency
90ºC is the maximum conductor temperature.
250ºC is the maximum short-circuit temperature (maximum 5 s).
-40ºC is the minimum service temperature for protected and fixed installations.
-0ºC is the minimum temperature required for handling and installation.
Performance of fire
non-propagation of flames according to IEC 60332-1 and EN 60332-1.
According to EN 60332-3, IEC 60332-3, and EN 50399, fire does not spread.
Low Smoke Halogen Free, or LSHF, is compliant with IEC 60754-1 and EN 60754-1.
According to EN 61034 and IEC 61034, low smoke emissions: Transmittance of light > 80%
low emissions of corrosive gases in accordance with IEC 60754-2 and UNE-EN 60754-2.
In accordance with EN 50575, the response to fire CPR is either B2ca s1a, d1, a1, or Cca-s1a, d1, a1.
Performance of mechanical systems
Bending radius minimum: x 5 cable diameter.
Medium severity AG2 impact resistance.
Performance of chemicals
Resistance to chemicals and oil: Acceptable.
In accordance with EN 50618, UV resistant.
Performance of water
Resistance to water: AD8 Submersion.
Other
marking from meter to meter.
Conditions of installation
Outside.
buried.
in a conduit.
Uses
industrial application.
public areas.
Design of the TOXFREE ZH RZ1 (AS) AL cable
The conductor
Class 2 aluminum according to N 60228 and IEC 60228.
Insulation
IEC 60502-1 defines cross-linked polyethylene (XLPE), while HD 603 defines type DIX-3.
In accordance with HD 308, insulated conductors are typically identified as follows:
One x Natural Two times Brown + Blue Three G: Green/Yellow + Brown + Blue Three times: Brown, Black, and Grey (reduced cross-section) 3 x + 1 x Brown + Black + Grey + Blue 4 G Green/Yellow + Black + Grey + Brown Four Brown, Black, Grey, and Blue 5 G Green/Yellow + Brown + Black + Grey + Blue Six or more Outer sheath in green/yellow with black numbers
Green Low Smoke Halogen Free (LSHF) polyolefin type ST8 (IEC 60502-1) and type DMZ-E (UNE 21123-4) polyolefin.
LOW VOLTAGE 0,6/1kV
UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034
Maximum service temperature: 90ºC.
Industrial use / Public places.
Technology
Class 2 conductor aluminum, based on IEC 60228 and UNE-EN 60228.
Cross-linked polyethylene (XLPE) for insulation.
In accordance with HD 308, insulated conductors are typically identified as follows:
One Natural
Two x Brown + Blue
3 G Green/Yellow + Brown + Blue
Three x Black + Grey + Brown
(reduced cross-section) 3 x + 1 x Brown + Black + Grey + Blue
4 G Green/Yellow + Black + Grey + Brown
Four Brown, Black, Grey, and Blue
5 G Green/Yellow + Brown + Black + Grey + Blue
Six or more Black digits plus green/yellow
Low Smoke Zero Halogen (LSZH) polyolefin type ST8 (IEC 60502-1) and type DMZ-E (UNE 21123-4) are the green outer sheaths.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
-
Chemical
Oil resistance: Acceptable.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
MECHANICAL PERFORMANCE
-
Impact resistance: AG2
Medium severity. -
Minimum bending radius:
x5 cable diameter.
WATER RESISTANCE
- Water resistance: AD8 Submersion.
CHEMICAL PERFORMANCE
- UV Resistant: based on UNE 211605.
FIRE PERFORMANCE
-
Fire non-propagation based on
EN 60332-3 / IEC 60332-3
/ EN 50399. - Flame non-propagation based on EN 60332-1 and IEC 60332-1
- Low corrosive gases emission according to IEC 60754-2
-
Low smoke emission according
to EN 61034 and IEC 61034: Light transmittance > 80%. - Low smoke emission according to EN 61034 and IEC 61034: Light transmittance > 80%.
- Reaction to fire CPR: Cca-s1a, d1, a1, based on EN 50575.
THERMAL PERFORMANCE
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum service temperature: -40ºC (fixed and protected installations)
APPROVALS
- AENOR
- CE
- KEMA KEUR
- RoHS
- SEC
- UKCA
BASED ON
- IEC 60502-1 / UNE 21123-4
National norm / European:
- UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034
APPROVALS
- Industrial use.
- Public places.
CONSTRUCTION PRODUCT REGULATION
- B2ca s1a, d1, a1
- B2ca s1b, d1, a1
INSTALLATION CONDITIONS
- Buried
- In conduit.
- Open Air.
International norm
- IEC 60332-1 / IEC 60332-3 / IEC 60754-1 / IEC 60754-2 / IEC 61034
OTHERS
- Meter by meter marking.