TOXFREE PLUS 331 ZH RZ1-K (AS+)
Description
LSHF and fire resistant power cable, for emergency circuits.
TOXFREE Plus 331 ZH RZ1-K (AS+) is a fire-resistant cable designed especially to ensure that emergency circuits would remain powered in the event of a fire. To guarantee life safety and a safe plant shutdown during a fire, essential circuits such as water pumps, fume extractors, acoustic alarms, and signage lights must operate. Therefore, it is highly recommended that it be used in public spaces such as hospitals, tunnels, offices, factories, laboratories, hotels, etc.
The TOXFREE PLUS 331 ZH RZ1-K (AS+) cable's functionality
Electrical performance
LOWEST VOLTAGE: 0.6/1 kV
Typical
IEC 60502-1
Acceptances
CE/RoHS
The cross-section-based regulations for CPR Construction Products are B2ca-s1a, d1, a1 or Cca-s1b, d1, a1.
Efficiency of heat
The maximum conductor temperature is 90ºC.
The highest short-circuit temperature (maximum 5 s) is 250ºC.
The minimum service temperature for fixed and protected installations is -40ºC.
The lowest temperature needed for handling and installation is -0ºC.
Mechanical system performance
Bending requires a minimum wire diameter of x5.
The AG2 impact resistance is medium.
Chemical performance
Oil and chemical resistance: Acceptable.
UV resistant in compliance with EN 50618.
Water's performance
Water does not harm AD5 Jets.
Fire performance
flames that do not spread in accordance with IEC 60332-1 and EN 60332-1.
In accordance with EN 60332-3, IEC 60332-3, and EN 50399 regulations, fire does not spread.
In accordance with IEC 60331-2 and EN 50200, fire resistance for Ø cable < 20 mm is (PH120) at 840°C for at least 120 minutes.
based on BS6387 categories C, W, and Z and IEC 60331-1 and EN 50362 for cables bigger than 20 mm.180' at 950ºC (cat C).
In accordance with BS6387 (300/500V) categories C, W, and Z, fire resistant 180' at 950ºC (cat C).
LSHF, or Low Smoke Halogen Free, complies with EN 60754-1 and IEC 60754-1.
Low smoke emissions are defined by EN 61034 and IEC 61034 as follows: Light transmittance > 60%
minimal corrosive gas emissions in compliance with EN 60754-2 and IEC 60754-2.
Other
identifying each meter separately.
Installation conditions
Outside.
interred.
within a conduit.
Applications
industrial use.
Emergency circuits
public spaces.
The TOXFREE PLUS 331 ZH RZ1-K (AS+) cable's design
The conductor
Copper that has been electrolytically annealed to Class 5 (flexible) in accordance with EN 60228 and IEC 60228.
Insulation
Mica tape + cross-linked polyethylene type DIX-3 is in accordance with HD 603.
Insulated conductors are generally designated in the following ways in compliance with HD 308:
Just One Natural
Twice Blue + Brown
Three x Grey + Blue + Brown
(decreased sectional area) Three times plus one brown, black, grey, and blue
Brown, Black, Grey, and Blue four times
Brown + Black + Grey + Yellow/Green + Blue is the Five G.
Sheath outside
Low Smoke Halogen Free (LSHF) polyolefin. It is orange in color, non-toxic, and fire retardant.
LOW VOLTAGE 0,6/1kV
Maximum conductor temperature: 90ºC.
Water resistance: AD5 Jets
Flame non-propagation based on EN 60332-1 and IEC 60332-1
Industrial use / Public places.
Technology
1. A conductor
Copper conductor that has been electrolytically annealed to Class 5 (flexible) in compliance with EN and IEC 60228.
2. Cozy
Cross-linked polyethylene (XLPE) is defined in IEC 60502-1.
Insulated conductors are generally designated in the following ways in compliance with HD 308:
Just One Natural
Brown + Blue x Two
3 G Brown + Blue + Green/Yellow
Three times Brown, Grey, and Black
(decreased sectional area) Three times plus one brown, black, grey, and blue
4 G Black + Grey + Brown + Yellow/Green
Brown, Black, Grey, and Blue four times
Five grams of grey, blue, yellow/green, black, and brown
3. The external covering
Low Smoke Halogen Free (LSHF) polyolefin. the color black.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
-
Chemical
Oil resistance: Acceptable.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
MECHANICAL PERFORMANCE
-
Impact resistance: AG2
Medium severity. -
Minimum bending radius:
x5 cable diameter.
WATER RESISTANCE
- Water resistance: AD8 Submersion.
CHEMICAL PERFORMANCE
- UV Resistant based on EN 50618.
FIRE PERFORMANCE
-
Fire non-propagation based on
EN 60332-3 / IEC 60332-3
/ EN 50399. - Flame non-propagation based on EN 60332-1 and IEC 60332-1
-
Low corrosive gases emission
based on UNE-EN 60754-2 and IEC 60754-2. -
Low smoke emission according
to EN 61034 and IEC 61034: Light transmittance > 80%.
THERMAL PERFORMANCE
-
Impact resistance: AG2 Medium
severity. -
Minimum bending radius: x5
cable diameter.
APPROVALS
- CE
- KEMA KEUR
INSTALLATION CONDITIONS
- Buried
- In conduit.
- Open Air.
National norm / European:
- UNE-EN 60332-1
CONSTRUCTION PRODUCT REGULATION
- B2ca s1a, d1, a1
BASED ON
- IEC 60502-1
International norm
- IEC 60502-1
OTHERS
- Meter by meter marking.