TOXFREE MARINE XZ1-K (AS)
Description
An LSHF safety cable is TOXFREE ZH YMz1Kf. It doesn't release any harmful or corrosive gases in the event of a fire, protecting people and electronic devices from potential harm. It is therefore strongly advised for use in public settings like hospitals, schools, museums, bus terminals, airports, shopping centres, offices, labs, etc.
Performance of the TOXFREE ZH YMz1Kf cable
Electrical functionality
MINIMUM VOLTAGE 0,6/1kV
Typical
UNE 21123-4 and IEC 60502-1
Acceptances
AENOR, SEC, KEMA KEUR, CE, and RoHS
Construction Product Regulation, or CPR
Depending on the cross-section, B2ca s1a, d1, a1 or Cca s1a, d1, a1
Thermal efficiency
90ºC is the maximum conductor temperature.
250ºC is the maximum short-circuit temperature (maximum 5 s).
For protected and fixed installations, the minimum service temperature is -40ºC.
-0ºC is the minimum temperature required for handling and installation.
Performance of fire
According to EN 60332-1/IEC 60332-1, flames do not spread.
In accordance with EN 60332-3/IEC 60332-3 and EN 50399, fire does not spread.
Low Smoke Halogen Free, or LSHF, is based on IEC 60754-1 and EN 60754-1.
Low smoke emission according to IEC 61034 and UNE-EN 61034: Light transmittance > 80%.
low emissions of corrosive gases in accordance with EN 60754-2/IEC 60754-2.
In accordance with EN 50575, the response to fire CPR is either B2ca s1a, d1, a1 or Cca s1a, d1, a1 (see cross-section).
Performance of mechanical systems
Cable diameter x5 is the minimum bending radius.
AG2 Medium severity impact resistance.
Performance of the environment
Oil and chemical resistance: Acceptable.
In accordance with EN 50618, UV resistant.
AD8 Submersion is water resistant.
Other
marking from meter to meter.
Conditions of installation
Outside.
buried.
in a conduit.
Uses
industrial application.
public areas.
Packing
available in drums and rolls (100 m in length).
Design of the TOXFREE ZH YMz1Kf cable
The conductor
Class 5 (flexible) electrolytic annealed copper conductor in accordance with EN and IEC 60228.
Insulation
IEC 60502-1 classifies cross-linked polyethylene as type XLPE, while HD 603 classifies it as type DIX-3. In accordance with HD 308, insulated conductors are typically identified as follows:
One Natural
Two times Brown + Blue
3 G Green/Yellow + Brown + Blue
Three x Black + Grey + Brown
(reduced cross-section) 3 x + 1 x Brown + Black + Grey + Blue
Four G: Brown, Black, Grey, and Green/Yellow
Four times: Brown, Black, Grey, and Blue
5 G Brown + Black + Grey + Blue + Green/Yellow
6 G or moreGreen/Yellow + Black numbered
External sheath
Polyolefin outer sheath for Low Smoke Halogen Free (LSHF), type ST8 in accordance with IEC 60502- 1 and type DMZ-E in accordance with UNE 21123-4. The colour green.
LOW VOLTAGE 0,6/1kV
Maximum conductor temperature: 90ºC.
Water resistance: AD5 Jets
Flame non-propagation based on EN 60332-1 and IEC 60332-1
Industrial use / Public places.
Technology
1. Conductor
Electrolytic annealed copper conductor, class 5 (flexible), based on EN 60228 and IEC 60228.
2. Insulation
Cross-linked polyethylene (XLPE) according to IEC 60502-1.
The standard identification of insulated conductors according to HD 308 is the following:
1 x Natural
2 x Blue + Brown
3 G Blue + Brown + Yellow/green
3 x Brown + Black + Grey
3 x + 1 x Brown + Black + Grey + Blue (reduced cross-section)
4 G Brown + Black + Grey + Yellow/green
4 x Brown + Black + Grey + Blue
5 G Brown + Black + Grey + Blue + Yellow/green
3. Outer sheath
Low Smoke Halogen Free (LSHF) polyolefin. Black colour.
Cable Specifications
ENVIRONMENTAL PERFORMANCE
-
Chemical
Oil resistance: Acceptable.
ELECTRICAL PERFORMANCE
- LOW VOLTAGE 0,6/1kV
MECHANICAL PERFORMANCE
-
Impact resistance: AG2
Medium severity. -
Minimum bending radius:
x5 cable diameter.
WATER RESISTANCE
- Water resistance: AD8 Submersion.
CHEMICAL PERFORMANCE
- UV Resistant based on EN 50618.
FIRE PERFORMANCE
-
Fire non-propagation based on
EN 60332-3 / IEC 60332-3
/ EN 50399. - Flame non-propagation based on EN 60332-1 and IEC 60332-1
-
Low corrosive gases emission
based on UNE-EN 60754-2 and IEC 60754-2. -
Low smoke emission according
to EN 61034 and IEC 61034: Light transmittance > 80%.
THERMAL PERFORMANCE
-
Impact resistance: AG2 Medium
severity. -
Minimum bending radius: x5
cable diameter.
APPROVALS
- CE
- KEMA KEUR
INSTALLATION CONDITIONS
- Buried
- In conduit.
- Open Air.
National norm / European:
- UNE-EN 60332-1
CONSTRUCTION PRODUCT REGULATION
- B2ca s1a, d1, a1
BASED ON
- IEC 60502-1
International norm
- IEC 60502-1
OTHERS
- Meter by meter marking.
Reviews
There are no reviews yet.